Gas cylinder cabinet Type 90 SUPREME L G90 90 cm

Gas cylinder cabinet Type 90 SUPREME L G90 90 cm

Regular price €4.221,00 VAT 0%
Regular price €4.063,00 Sale price €4.221,00 VAT 0%
Sale Sold out
Shipping calculated at checkout.

SKU:79-200960-021

Estimated delivery time: 8-10 weeks

Warranty: 2 years

By requesting a quote, you will receive model-specific product prices.

The Düperthal SUPREME standard L is a Type G90 safety storage cabinet for pressurised gas cylinders, with 90-minute fire protection tested to DIN EN 14470-2. It allows gas cylinders to be stored safely inside the building, close to the point of use.

Optimised ventilation ducts provide an efficient air flow that extracts any escaping gas, and the exhaust air connection on the roof allows connection to technical ventilation. The total volume of the stored gas cylinders may be up to 220 l (EN 14470-2). For flammable or oxidising gases the cabinet needs at least 10-fold air exchange (5.3 m³/h), and for acutely toxic gases at least 120-fold (63 m³/h, pressure drop 34 Pa). Cylinders are secured with 3 retaining belts, and marked drill areas make it easy to route gas lines and cables; purge gas line connections are available as an option. External dimensions are 610 x 895 x 2030 mm (D x W x H).

Typical applications:

  • Storage of technical, flammable, oxidising and toxic gases in laboratories
  • Supplying gas to instruments directly from the cabinet
  • Indoor gas cylinder storage according to TRGS 510

Key highlights:

  • Type G90: 90-minute fire resistance (DIN EN 14470-2)
  • Max. total cylinder volume 220 l (EN 14470-2)
  • Efficient gas extraction through optimised ventilation ducts
  • 3 cylinder retaining belts, max. load 300 kg
  • Long service life: 90,000-cycle door endurance test
  • TÜV SÜD GS mark and High Quality Certificate
  • 2-year warranty

BROCHURES

View full details

Your added advantage with the SUPREME line!

  • The highest fire protection for your safety
    Maximum safety with Type G90 technology for a continuous fire protection concept that meets the highest standards.

  • Upper-level style for your health
    Optimised ventilation ducts provide an efficient air flow system to extract any escaping gas within the cabinet.

  • Increased lifetime for your investment
    Duration test acc. to DIN EN 16121/16122, but 80,000 instead of 50,000 cycles in dynamic load test.
  • 1. Ventilation

    Efficient ventilation in each cabinet level and the possibility of connecting the purging gas pipes directly to the exhaust air duct.

  • 2. Penetration of gas pipes and cables

    Drilling areas for the penetration of pipes or cables are marked on the cabinet roof and side panels.

  • 3. Fittings

    Maximum flexibility through adjustable installation rails as a standard - ideal to read the fittings ergonomically and without reflections. Alternatively, an upright installation is possible.

  • 4. Door technology

    The cabinet doors may be opened up to an angle of 170 degrees, thus offering the user maximum freedom of use. The opening angle can be adjusted continuously.

  • 5. Use of space

    The interior height is optimised for the installation and operation of gas cylinder fittings.

  • 6. Transport

    Gas cylinders can be easily put in place using the robust roll-in flap or the gas cylinder trolley for 10 litre (2.64 gal) gas cylinders.